PS1:When the cooling tower and cooling water pump are at the lowest point at the same time:

1. Install an exhaust valve at the highest point of the water system;

2. Install a check valve at the horizontal position of the water outlet of the pump to avoid water backflow in the cooling system;

3. The pump head must be greater than [(the difference between the highest and lowest points of the cooling system) + system pressure];

4. Install the electric two-way valve at the horizontal position of the water inlet of the cooling tower. When the unit is stopped, the electric two-way valve is closed to avoid water backflow in the system.

What should we watch out for when the cooling tower and pump are at the lowest point of the system